Jump to content

Huntington Beach Energy Project

Coordinates: 33°38′42″N 117°58′35″W / 33.64500°N 117.97639°W / 33.64500; -117.97639
From Wikipedia, the free encyclopedia

Huntington Beach Energy Project
Map
Official nameHuntington Beach Energy Project
CountryUnited States
LocationHuntington Beach, California
Coordinates33°38′42″N 117°58′35″W / 33.64500°N 117.97639°W / 33.64500; -117.97639
StatusOperational
Construction beganUnits 1-4: 1958
Unit 5: June 2017
Commission dateUnits 1-4: 1967
Unit 5: February 4, 2020 [1]
Decommission dateUnits 1: December 31, 2019 [2]
Unit 2: December 31, 2020 (expected)
Unit 3: ?
Unit 4: ?
OwnerAES Corporation
OperatorAES Corporation
Thermal power station
Primary fuelNatural gas
Cooling sourceUnit 2: Pacific Ocean
Unit 5: Atmosphere
Combined cycle?Yes
Power generation
Units operational1 x 225 MW CCGT
1 x 644 MW CCGT
Units planned1 x 200 MW SCGT
Units decommissioned1 x 225 MW CCGT
2 x ? MW
Nameplate capacity869 MW

The Huntington Beach Energy Project (HBEP), formerly AES Huntington Beach, is a natural gas-fired power station located in Huntington Beach, California.

History

[edit]

The facility was constructed between 1958 and 1969 on a 53-acre site (21 ha).[3] Total station capacity was 1,000,000 kilowatts. It originally consisted of two 215 MW General Electric cross compound 3600/1800 RPM steam turbines (HP/LP turbines). Main steam pressure was 2400 PSI, main steam temperature was 1050 DEG F and reheat temperature was 1000 DEG F. The generators were hydrogen cooled, rated at 128,000 KVA. The boilers were Babcock and Wilcox natural circulation (drum boilers), rated at 1,560,000 LB/HR. The boilers could be fired with natural gas or fuel oil. Units 1 and 2 were completed in 1958. Unit 3 was a General Electric cross compound 3600/1800 RPM at 1050/1000 DEG F, with a 215 MW steam turbine. Unit 4 was a Westinghouse, cross compound 3600/1800 rpm, 1050/1000 DEG F 225MW. The boilers were Babcox and Wilcox Universal Pressure Boilers (called once thru) rated at 1,638,000 LB/HR. All four units were cooled using water sourced from the Pacific Ocean. Unit 5 was completed in 1969 and was a gas peaking unit, rated at 121 MW at 90 deg F. It consisted of 8 Pratt & Whitney GG4a-2 gas turbines exhausting into 4 Worthington expanders 2 stage turbines and 1 Westinghouse generator, 3 phase hydrogen cooled rated at 162,500 KVA, 16,000 volts 3600 rpm. Unit 1 was decommissioned on December 31, 2019, while Units 3 and 4 were decommissioned at an unknown date. Unit 2 is the only original unit still in operation.[2]

In June 2017, AES began construction of a 644 MW combined cycle gas turbine (Unit 5) that is visually smaller and is air-cooled.[4] Unit 5 was commissioned on February 4, 2020. An additional 200 MW simple cycle gas turbine is proposed for the site should additional capacity be necessary.[5][1]

See also

[edit]

References

[edit]
  1. ^ a b "More environment-friendly power generators go online in Huntington Beach". Orange County Register. February 12, 2020. Retrieved February 16, 2020.
  2. ^ a b "AES Huntington Beach - The Power of Positive Energy". www.renewaeshuntington.com. Retrieved February 16, 2020.
  3. ^ Vega, Priscella (January 3, 2019). "Major construction work scheduled to be completed this year for modernized AES power plant in Huntington Beach". Daily Pilot. Los Angeles Times. Retrieved March 28, 2022.
  4. ^ Vega, Priscella (August 21, 2019). "New power plant in Huntington Beach is 91% complete, AES says". Daily Pilot. Los Angeles Times. Retrieved March 29, 2022.
  5. ^ "Facilities: Huntington Beach | AES California". www.aescalifornia.com. Archived from the original on March 23, 2018. Retrieved February 16, 2020.